[Products]
Analog » Power Supplies
FN-300-ULX
Power Supply
STANDARD FEATURES
  • Input 115VAC / 60Hz, 1.45 amp.
  • 12VDC or 24VDC selectable output.
  • Class 2 Rated power limited output.
  • Input fuse rated @ 3.5 amp/250V.
  • Filtered and electronically regulated output.
  • Short circuit and thermal overload protection.
  • AC fail supervision (form C contacts).
  • Low battery supervision (form C contacts).
  • Battery presence supervision (form C contacts).
  • Built-in charger for sealed lead acid or gel type batteries.
  • Automatic switch over to stand-by battery when AC fails.
  • Maximum charge current .7 amp.
  • Zero voltage drop when switched over to battery backup.
  • AC input and DC output LED indicators.
  • Accommodates up to two (2) 12VDC/7AH batteries.
  • Power supply, enclosure, cam lock and battery leads.
FN-400-ULX
Power Supply
STANDARD FEATURES
  • Input 115VAC / 60Hz, 1.45 amp.
  • 12VDC or 24VDC selectable output.
  • Single Class 2 Rated power limited output.
  • Input fuse rated @ 3.5 amp/250V.
  • Filtered and electronically regulated output.
  • Short circuit and thermal overload protection.
  • AC fail supervision (form C contacts).
  • Low battery supervision (form C contacts).
  • Battery presence supervision (form C contacts).
  • Built-in charger for sealed lead acid or gel type batteries.
  • Automatic switch over to stand-by battery when AC fails.
  • Maximum charge current .7 amp.
  • Zero voltage drop when switched over to battery backup.
  • AC input and DC output LED indicators.
  • Accommodates up to two (2) 12VDC/7AH batteries.
  • Power supply, enclosure, cam lock and battery leads.
FN-600-ULX
Power Supply
STANDARD FEATURES
  • Input 115VAC / 60Hz, 1.45 amp.
  • 12VDC or 24VDC selectable output.
  • Single Class 2 Rated power limited output.
  • Input fuse rated @ 3.5 amp/250V.
  • Filtered and electronically regulated output.
  • Short circuit and thermal overload protection.
  • AC fail supervision (form C contacts).
  • Low battery supervision (form C contacts).
  • Battery presence supervision (form C contacts).
  • Built-in charger for sealed lead acid or gel type batteries.
  • Automatic switch over to stand-by battery when AC fails.
  • Maximum charge current .7 amp.
  • Zero voltage drop when switched over to battery backup.
  • AC input and DC output LED indicators.
  • Accommodates up to two (2) 12VDC/7AH batteries.
  • Power supply, enclosure, cam lock and battery leads.
FN-1024-ULX
Power Supply
STANDARD FEATURES
  • Input 115VAC / 60Hz, 4.4 amp.
  • 24VDC output.
  • Single non-power limited output.
  • Input fuse rated @ 3.5 amp/250V.
  • Filtered and electronically regulated output.
  • Short circuit and thermal overload protection.
  • AC fail supervision (form C contacts).
  • Low battery supervision (form C contacts).
  • Battery presence supervision (form C contacts).
  • Built-in charger for sealed lead acid or gel type batteries.
  • Automatic switch over to stand-by battery when AC fails.
  • Maximum charge current 3.6 amp.
  • Zero voltage drop when switched over to battery backup.
  • AC input and DC output LED indicators.
  • Accommodates up to two (2) 12VDC/7AH batteries.
  • Power supply, enclosure, cam lock and battery leads.
FN-642-ULADA
Power Extenders
STANDARD FEATURES
  • Two (2) Class A or two (2) Class B FACP inputs.
  • Two (2) NC dry contact trigger inputs.
  • Four (4) Class A or four (4) Class B indicating circuits.
  • Two (2) Class B outputs may be paralleled for more power on an indicating circuit.
  • One (1) Aux. Power Output @ 1 amp supply current (w/battery back up).
  • One (1) Aux. Power Output @ 1 amp supply current (w/o battery back up)
  • Signal Circuit Trouble Memory - facilitates quickly locating intermittent system trouble and eliminates costly and unnecessary service calls. LEDs indicate a prior fault (short, open, ground) has occurred on one or more signaling circuit outputs.
  • 2 wire Horn/Strobe Sync mode allows audible notification appliances (Horns) to be silenced while visual notification appliances (Strobes) continue to operate.
FN-842-ULADA
Power Extenders
STANDARD FEATURES
  • Two (2) Class A or two (2) Class B FACP inputs.
  • Two (2) NC dry contact trigger inputs.
  • Four (4) Class A or four (4) Class B indicating circuits.
  • Two (2) Class B outputs may be paralleled for more power on an indicating circuit.
  • One (1) Aux. Power Output @ 1 amp supply current (w/battery back up).
  • One (1) Aux. Power Output @ 1 amp supply current (w/o battery back up)
  • Signal Circuit Trouble Memory - facilitates quickly locating intermittent system trouble and eliminates costly and unnecessary service calls. LEDs indicate a prior fault (short, open, ground) has occurred on one or more signaling circuit outputs.
  • 2 wire Horn/Strobe Sync mode allows audible notification appliances (Horns) to be silenced while visual notification appliances (Strobes) continue to operate.
FN-1042-ULADA
Power Extenders
STANDARD FEATURES
  • Two (2) Class A or two (2) Class B FACP inputs.
  • Two (2) NC dry contact trigger inputs.
  • Four (4) Class A or four (4) Class B indicating circuits.
  • Two (2) Class B outputs may be paralleled for more power on an indicating circuit.
  • One (1) Aux. Power Output @ 1 amp supply current (w/battery back up).
  • One (1) Aux. Power Output @ 1 amp supply current (w/o battery back up)
  • Signal Circuit Trouble Memory - facilitates quickly locating intermittent system trouble and eliminates costly and unnecessary service calls. LEDs indicate a prior fault (short, open, ground) has occurred on one or more signaling circuit outputs.
  • 2 wire Horn/Strobe Sync mode allows audible notification appliances (Horns) to be silenced while visual notification appliances (Strobes) continue to operate.