| Conventional » Alarm Control Panel | HCP-204E (Discontinued)4-Zone Expandable Fire Alarm Control Panel |
STANDARD FEATURES - 4 Class B (Style B) Initiating Circuits which may be configured as 2 Class A (Style D) circuits. Expandable up to 8 Class B (Style B) or 4 Class A (Style D) Initiating Circuits.
- 2 Class A/B (Style Z/Y) Indicating Circuits with individual trouble indicators (1.7 Amps max. per circuit). Expandable up to 4 Class A/B (Style Z/Y) Indicating Circuits.
- Each Indicating Circuit can be configured as Silenceable or Non-Silenceable. Audibles may be configured as Steady, Temporal Code, California Code or March Time.
- Output for RTI or Remote Annunciators of 24 VDC, 300 mA max, unfiltered
- Built-in Walk Test operation
- Auxiliary relay contacts for Common Alarm, Common Trouble and Common Supervisory. If no Supervisory circuits are enabled, the Supervisory relay becomes a second alarm relay.
- 6 Amp power supply
- Easy configuration via DIP switches
| HCP-204 (Discontinued)4-Zone Fire Alarm Control Panel |
STANDARD FEATURES - 4 Class B (Style B) Initiating Circuits which may be configured as 2 Class A (Style D) circuits
- 2 Class A/B (Style Z/Y) Indicating Circuits with individual trouble indicators (1.25 Amps max. per circuit)
- Each Indicating Circuit can be configured as Silenceable or Non-Silenceable. Audible may be configured as Steady, Temporal Code, California Code or March Time
- Selectable alarm verification on initiating circuits
- Output for 4-wire resettable regulated smoke power supply of 24 VDC 100 mA maximum
- Output for RTI or Remote Annunciators of 24 VDC, 300 mA max, unfiltered
- Built-in Walk Test operation
- Auxiliary relay contacts for Common Alarm, Common Trouble and Common Supervisory. If no Supervisory circuits are enabled, the Supervisory relay becomes a second Alarm relay.
- 2.75 Amp power supply
- Easy configuration via DIP switches
| HCP-202 (Discontinued)2-Zone Fire Alarm Control Panel |
STANDARD FEATURES - 2 Class B (Style B) Initiating Circuits which may be configured as 1 Class A (Style D) circuits
- 2 Class A/B (Style Z/Y) Indicating Circuits with individual trouble indicators (1.25 Amps max. per circuit)
- Each Indicating Circuit can be configured as Silenceable or Non-Silenceable. Audible may be configured as Steady, Temporal Code, California Code or March Time
- Selectable alarm verification on initiating circuits
- Output for 4-wire resettable regulated smoke power supply of 24 VDC 100 mA maximum
- Output for RTI or Remote Annunciators of 24 VDC, 300 mA max, unfiltered
- Built-in Walk Test operation
- Auxiliary relay contacts for Common Alarm, Common Trouble and Common Supervisory. If no Supervisory circuits are enabled, the Supervisory relay becomes a second Alarm relay.
- 2.75 Amp power supply
- Easy configuration via DIP switches
| HCP-1008E8-Zone Expandable Fire Alarm Control Panel |
STANDARD FEATURES - 8 Class B (Style B) Initiating Circuits which may be configured as 4 Class A (Style D) Circuits. Expandable up to 24 Class B or 12 Class A Initiating Circuits.
- 4 Class A/B (Style Z/Y) Indicating Circuits with individual trouble indicators (1.7 Amps max. per circuit)
- Each Indicating Circuit can be configured as Silenceable or Non-Silenceable. Audible may be configured as Steady, Temporal Code, California Code or March Time.
- Each Initiating Circuit can be configured as Alarm, Supervisory, Waterflow or Trouble
- Two outputs for 4 wire resetable smoke power supply (200 mA max. each)
- Alarm verification on Initiating Circuits
- Easy configuration via push buttons and SLIDE switches on the front panel
|